23.01.2015 Views

NXS Form 63-2600, Users Manual, Technical Data - CONTROL ...

NXS Form 63-2600, Users Manual, Technical Data - CONTROL ...

NXS Form 63-2600, Users Manual, Technical Data - CONTROL ...

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Honeywell Description of Parameters 175<br />

609 Torque limit 6 (2.10.1)<br />

With this parameter you can set the torque limit control between 0.0 – 300.0 %.<br />

610 Torque limit control P-gain 6 (2.10.1)<br />

This parameter defines the gain of the torque limit controller. It is used in Open Loop<br />

control mode only.<br />

611 Torque limit control I-gain 6 (2.10.2)<br />

This parameter determines the I-gain of the torque limit controller. It is used in Open<br />

Loop control mode only.<br />

612 CL: Magnetizing current 23456 (2.6.4.1, 2.6.27.1)<br />

Set here the motor magnetizing current (no-load current). See chapter 9.2.<br />

613 CL: Speed control P gain 23456 (2.6.4.2, 2.6.27.2)<br />

Sets the gain for the speed controller in % per Hz. See chapter 9.2.<br />

614 CL: Speed control I time 23456 (2.6.4.3, 2.6.27.3)<br />

Sets the integral time constant for the speed controller. Increasing the I-time increases<br />

stability but lengthens the speed response time. See chapter 9.2.<br />

615 CL: Zero speed time at start 23456 (2.6.4.9, 2.6.27.9)<br />

After giving the start command the drive will remain at zero speed for the time defined by<br />

this parameter. The ramp will be released to follow the set frequency/speed reference<br />

after this time has elapsed from the instant where the command is given. See chapter<br />

9.2.<br />

616 CL: Zero speed time at stop 23456 (2.6.4.10, 2.6.27.10)<br />

The drive will remain at zero speed with controllers active for the time defined by this<br />

parameter after reaching the zero speed when a stop command is given. This parameter<br />

has no effect if the selected stop function (ID506) is Coasting. See chapter 9.2.<br />

617 CL: Current control P gain 23456 (2.6.4.17, 2.6.27.17)<br />

Sets the gain for the current controller. This controller is active only in closed loop and<br />

advanced open loop modes. The controller generates the voltage vector reference to the<br />

modulator. See chapter 9.2.<br />

618 CL: Encoder filter time 23456 (2.6.4.15, 2.6.27.15)<br />

Sets the filter time constant for speed measurement.<br />

The parameter can be used to eliminate encoder signal noise. Too high a filter time<br />

reduces speed control stability. See chapter 9.2.<br />

619 CL: Slip adjust 23456 (2.6.4.6, 2.6.27.6)<br />

The motor name plate speed is used to calculate the nominal slip. This value is used to<br />

adjust the voltage of motor when loaded. The name plate speed is sometimes a little<br />

inaccurate and this parameter can therefore be used to trim the slip. Reducing the slip<br />

adjust value increases the motor voltage when the motor is loaded. See chapter 9.2.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!