74 Multi-purpose Control Application Honeywell<br />

6.6.4 Input signals<br />

6.6.4.1 Basic Settings (Control keypad: Menu M2 G2.2.1)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

Start signal<br />

1<br />

(Default:<br />

DIN1)<br />

Start<br />

signal 2<br />

(Default:<br />

DIN2)<br />

P2.2.1.1<br />

P2.2.1.2<br />

P2.2.1.3<br />

Start/Stop logic<br />

selection<br />

Motor potentiometer<br />

ramp time<br />

Motor potentiometer<br />

frequency reference<br />

memory reset<br />

0 7 0 300<br />

0,1 2000,0 Hz/s 10,0 331<br />

0 2 1 367<br />

P2.2.1.4 Adjust input 0 5 0 493<br />

P2.2.1.5 Adjust minimum 0,0 100,0 % 0,0 494<br />

P2.2.1.6 Adjust maximum 0,0 100,0 % 0,0 495<br />

Table 6-6. Input signals: basic settings, G2.2.1<br />

6.6.4.2 Analogue input 1 (Control keypad: Menu M2 G2.2.2)<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

Start forw.<br />

Start/Stop<br />

Start/Stop<br />

Start pulse<br />

Start<br />

Fwd pulse<br />

Start pulse<br />

Start pulse<br />

Start rev.<br />

Reverse<br />

Run enable<br />

Stop pulse<br />

Mot.pot.UP<br />

Rev pulse<br />

Rev pulse<br />

Enabl pulse<br />

0=No reset<br />

1=Reset if stopped or<br />

powered down<br />

2=Reset if powered down<br />

0=Not used<br />

1=AI1<br />

2=AI2<br />

3=AI3<br />

4=AI4<br />

5=Fieldbus (FBProcess<strong>Data</strong>IN3)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.2.2.1<br />

AI1 signal<br />

selection<br />

0 A.1 377<br />

P2.2.2.2 AI1 filter time 0,00 10,00 s 0,10 324 0=No filtering<br />

P2.2.2.3 AI1 signal range 0 3 0 320<br />

0=0…100%*<br />

1=20…100%*<br />

2= -10V…+10V*<br />

3= Custom range*<br />

P2.2.2.4<br />

AI1 custom minimum<br />

-160,00<br />

setting<br />

160,00 % 0,00 321<br />

P2.2.2.5<br />

AI1 custom<br />

maximum setting<br />

-160,00 160,00 % 100,00 322<br />

P2.2.2.6<br />

AI1 reference<br />

scaling, minimum<br />

value<br />

0,00 320,00 Hz 0,00 303<br />

Selects the frequency that<br />

corresponds to the min.<br />

reference signal<br />

P2.2.2.7<br />

P2.2.2.8<br />

AI1 reference<br />

scaling, maximum<br />

value<br />

AI1 joystick<br />

0,00 320,00 Hz 0,00 304<br />

0,00 20,00 % 0,00 384<br />

Selects the frequency that<br />

corresponds to the max.<br />

reference signal<br />

hysteresis<br />

P2.2.2.9 AI1 sleep limit 0,00 100,00 % 0,00 385<br />

P2.2.2.10 AI1 sleep delay 0,00 320,00 s 0,00 386<br />

P2.2.2.11 AI1 joystick offset -100,00 100,00 % 0,00 165<br />

Table 6-7. Analogue input 1 parameters, G2.2.2<br />

*Remember to place jumpers of block X2 accordingly.<br />

See the product's User's <strong>Manual</strong><br />

Automation and Control Solutions<br />

Honeywell<br />