Honeywell Description of Parameters 169<br />

1 The frequency drive is able to start into a running motor by applying a small<br />

torque to motor and searching for the frequency corresponding to the speed<br />

the motor is running at. Searching starts from the maximum frequency towards<br />

the actual frequency until the correct value is detected. Thereafter, the output<br />

frequency will be increased/decreased to the set reference value according to<br />

the set acceleration/deceleration parameters.<br />

Use this mode if the motor is coasting when the start command is given. With<br />

the flying start it is possible to ride through short mains voltage interruptions.<br />

506 Stop function (2.4.7)<br />

Coasting:<br />

0 The motor coasts to a halt without any control from the frequency drive, after<br />

the Stop command.<br />

Ramp:<br />

1 After the Stop command, the speed of the motor is decelerated according to<br />

the set deceleration parameters.<br />

If the regenerated energy is high it may be necessary to use an external<br />

braking resistor for faster deceleration.<br />

Normal stop: Ramp/ Run Enable stop: coasting<br />

2 After the Stop command, the speed of the motor is decelerated according to<br />

the set deceleration parameters. However, when Run Enable is selected, the<br />

motor coasts to a halt without any control from the frequency drive.<br />

Normal stop: Coasting/ Run Enable stop: ramping<br />

3 The motor coasts to a halt without any control from the frequency drive.<br />

However, when Run Enable signal is selected, the speed of the motor is<br />

decelerated according to the set deceleration parameters. If the regenerated<br />

energy is high it may be necessary to use an external braking resistor for<br />

faster deceleration.<br />

507 DC-braking current 234567 (2.4.8)<br />

Defines the current injected into the motor during DC-braking.<br />

508 DC-braking time at stop 234567 (2.4.9)<br />

Determines if braking is ON or OFF and the braking time of the DC-brake when the<br />

motor is stopping. The function of the DC-brake depends on the stop function, parameter<br />

ID506.<br />

0 DC-brake is not used<br />

>0 DC-brake is in use and its function depends on the Stop function,<br />

(param. ID506). The DC-braking time is determined with this parameter.<br />

Par. ID506 = 0; Stop function = Coasting:<br />

After the stop command, the motor coasts to a stop without control of the frequency<br />

drive.<br />

With DC-injection, the motor can be electrically stopped in the shortest possible time,<br />

without using an optional external braking resistor.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!