194 Description of Parameters Honeywell<br />

1020 PID controller bypass 7 (2.9.16)<br />

With this parameter, the PID controller can be programmed to be bypassed. Then the<br />

frequency of the controlled drive and the starting points of the auxiliary drives are<br />

defined according to the actual value signal. See Figure 8-58.<br />

Output freq.<br />

Max. freq.<br />

(par. ID102)<br />

Start freq. of the aux. drive 1<br />

(par. ID1002)<br />

Start freq. of the aux. drive 2<br />

(par. ID1004)<br />

Minimum freq.<br />

(par. ID101)<br />

Stop freq. of the aux.<br />

drive 1 (par. ID1003)<br />

Stop freq. of the aux.<br />

drive 2 (par. ID1005)<br />

Actual value<br />

Minimum of the<br />

actual value<br />

Maximum of the<br />

actual value<br />

Start/stop control of<br />

the freq. converter stop<br />

start<br />

start<br />

Auxiliary drive 1<br />

stop<br />

start<br />

Auxiliary drive 2<br />

Figure 8-58. Example of variable speed drive and two auxiliary drives with bypassed PID<br />

controller<br />

1021 Analogue input selection for input pressure measurement 7 (2.9.17)<br />

1022 Input pressure high limit 7 (2.9.18)<br />

1023 Input pressure low limit 7 (2.9.19)<br />

1024 Output pressure drop value 7 (2.9.20)<br />

NX12k91<br />

In pressure increase stations there may be need for decreasing the output pressure if<br />

the input pressure decreases below a certain limit. The input pressure measurement<br />

which is needed is connected to the analogue input selected with parameter ID1021.<br />

See Figure 8-59.<br />

stop<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!