188 Description of Parameters Honeywell<br />

738 Automatic restart: Number of tries after underload fault trip (2.8.10)<br />

This parameter determines how many automatic restarts can be made during the trial<br />

time set by parameter ID718.<br />

0 = No automatic restart after Underload fault trip<br />

>0 = Number of automatic restarts after Underload fault trip<br />

739 Number of PT100 inputs in use 567 (2.7.24)<br />

If you have a PT100 input board installed in your frequency drive you can choose here<br />

the number of PT100 inputs in use. See also the I/O boards manual.<br />

Note: If the selected value is greater than the actual number of used PT100 inputs, the<br />

display will read 200ºC. If the input is short-circuited the displayed value is –30ºC.<br />

740 Response to PT100 fault 567 (2.7.25)<br />

0 = No response<br />

1 = Warning<br />

2 = Fault, stop mode after fault according to ID506<br />

3 = Fault, stop mode after fault always by coasting<br />

741 PT100 warning limit 567 (2.7.26)<br />

Set here the limit at which the PT100 warning will be activated.<br />

742 PT100 fault limit 567 (2.7.27)<br />

Set here the limit at which the PT100 fault (F56) will be activated.<br />

750 Cooling monitor 6 (2.2.7.23)<br />

When using a water-cooled drive, connect this input to the Cooling OK signal from flow<br />

control application. The parameter is available for NXP drives only.<br />

751 Cooling fault delay<br />

The delay after the motor is stopped with coasting after the cooling OK signal is missing.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!