Honeywell Pump and Fan Control Application 101<br />

This level is defined as follows:<br />

• If the number of running auxiliary drives is smaller than the value of parameter<br />

2.9.27 the autochange function can take place.<br />

• If the number of running auxiliary drives is equal to the value of parameter 2.9.27<br />

and the frequency of the controlled drive is below the value of parameter 2.9.28 the<br />

autochange can take place.<br />

• If the value of parameter 2.9.28 is 0.0 Hz, the autochange can take place only in rest<br />

position (Stop and Sleep) regardless of the value of parameter 2.9.27.<br />