168 Description of Parameters Honeywell<br />

500 Acceleration/Deceleration ramp 1 shape 234567 (2.4.1)<br />

501 Acceleration/Deceleration ramp 2 shape 234567 (2.4.2)<br />

The start and end of acceleration and deceleration ramps can be smoothed with these<br />

parameters. Setting value 0 gives a linear ramp shape which causes acceleration and<br />

deceleration to act immediately to the changes in the reference signal.<br />

Setting value 0.1…10 seconds for this parameter produces an S-shaped<br />

acceleration/deceleration. The acceleration time is determined with parameters<br />

ID103/ID104 (ID502/ID503).<br />

[Hz]<br />

ID103, ID104<br />

(ID502, ID503)<br />

ID500 (ID501)<br />

ID500 (ID501)<br />

[t]<br />

Figure 8-42. Acceleration/Deceleration (S-shaped)<br />

502 Acceleration time 2 234567 (2.4.3)<br />

503 Deceleration time 2 234567 (2.4.4)<br />

These values correspond to the time required for the output frequency to accelerate from<br />

the zero frequency to the set maximum frequency (par. ID102). These parameters give<br />

the possibility to set two different acceleration/deceleration time sets for one application.<br />

The active set can be selected with the programmable signal DIN3 (par. ID301).<br />

504 Brake chopper 234567 (2.4.5)<br />

0 = No brake chopper used<br />

1 = Brake chopper in use and tested when running. Can be tested also in READY<br />

state<br />

2 = External brake chopper (no testing)<br />

3 = Used and tested in READY state and when running<br />

4 = Used when running (no testing)<br />

When the frequency drive is decelerating the motor, the inertia of the motor and the load<br />

are fed into an external brake resistor. This enables the frequency drive to decelerate<br />

the load with a torque equal to that of acceleration (provided that the correct brake<br />

resistor has been selected). See separate Brake resistor installation manual.<br />

505 Start function (2.4.6)<br />

Ramp:<br />

0 The frequency drive starts from 0 Hz and accelerates to the set reference<br />

frequency within the set acceleration time. (Load inertia or starting friction may<br />

cause prolonged acceleration times).<br />

Flying start:<br />

NX12K20<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!