110(110) Fault tracing<br />

43 Encoder fault Note the exceptional Fault data record.<br />

See 7.3.4.3. Additional codes:<br />

1 = Encoder 1 channel A is missing<br />

2 = Encoder 1 channel B is missing<br />

3 = Both encoder 1 channels are missing<br />

4 = Encoder reversed<br />

50 Analog input I in < Current at the analogue input is < 4mA.<br />

4mA (selected − control cable is broken or loose<br />

signal range 4 to − signal source has failed<br />

20 mA)<br />

51 External fault Digital input fault.<br />

52 Keypad commu-<br />

The connection between the control key-<br />

Check encoder channel connections.<br />

Check the encoder board.<br />

Check the current loop circuitry.<br />

Check keypad connection and possible<br />

nication fault pad and the freq. drive is broken.<br />

keypad cable.<br />

53 Fieldbus fault The data connection between the fieldbus Check installation.<br />

Master and the fieldbus board is broken. If installation is correct contact your<br />

nearest distributor.<br />

54 Slot fault Defective option board or slot Check board and slot.<br />

Contact your nearest distributor.<br />

56 PT100 board<br />

Find the cause of temperature rise<br />

temp. fault<br />

Table 9-1. Fault codes<br />

Temperature limit values set for the<br />

PT100 board parameters have been<br />

exceeded<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com<br />

9

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!