Honeywell Description of Parameters 191<br />

Output frequency<br />

Output frequency<br />

Start delay of the aux.<br />

drives (par. ID1010)<br />

Start freq. of aux. drive 1 (par. ID1002 + 1 Hz)<br />

Frequency after starting<br />

the aux. drive1<br />

is par. ID1003 - 1 Hz<br />

Start freq. of aux. drive 1<br />

(par. ID1002 + 1 Hz)<br />

Frequency<br />

increase<br />

during the<br />

start delay<br />

Stop freq. of aux.<br />

drive 1<br />

(par. ID1003 - 1 Hz)<br />

Fmin<br />

par. ID101<br />

Stop freq. of aux. drive 1<br />

(par. ID1003 - 1 Hz)<br />

Frequency after starting<br />

the aux. drive1<br />

is par. ID1003 + 1 Hz<br />

Flow<br />

Frequency<br />

decrease during<br />

Fmin the stop delay<br />

par. ID101<br />

NX12k89<br />

Stop delay of the aux.<br />

drives (par. ID1011)<br />

Figure 8-54. Example of parameter setting; Variable speed drive and one auxiliary drive<br />

Flow<br />

1012 Reference step after start of auxiliary drive 1 7 (2.9.12)<br />

1013 Reference step after start of auxiliary drive 2 7 (2.9.13)<br />

1014 Reference step after start of auxiliary drive 3 7 (2.9.14)<br />

1015 Reference step after start of auxiliary drive 4 7 (2.9.15)<br />

The reference step will be automatically added to the reference value always when the<br />

corresponding auxiliary drive is started. With the reference steps e.g. the pressure loss<br />

in the piping caused by the increased flow can be compensated. See Figure 8-55.<br />

Reference for PI-controller<br />

Reference step 3<br />

par. ID1014<br />

Reference step 1<br />

par. ID1012<br />

Reference step 2<br />

par. ID1013<br />

Reference<br />

(analogue<br />

input)<br />

Time<br />

Aux. drive 1<br />

Aux. drive 2<br />

stop<br />

start<br />

stop<br />

start<br />

Aux. drive 3<br />

stop<br />

start<br />

Figure 8-55. Reference steps after starting auxiliary drives<br />

NX12k90<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com