192 Description of Parameters Honeywell<br />

1016 Sleep frequency 57 (2.1.15)<br />

The frequency drive is stopped automatically if the frequency of the drive falls below the<br />

Sleep level defined with this parameter for a time greater than that determined by<br />

parameter ID1017. During the Stop state, the PID controller is operating switching the<br />

frequency drive to Run state when the actual value signal either falls below or exceeds<br />

(see par. ID1019) the Wake-up level determined by parameter ID1018. See Figure 8-56.<br />

1017 Sleep delay 57 (2.1.16)<br />

The minimum amount of time the frequency has to remain below the Sleep level before<br />

the frequency drive is stopped. See Figure 8-56.<br />

1018 Wake-up level 57 (2.1.17)<br />

The wake-up level defines the level below which the actual value must fall or which has<br />

to be exceeded before the Run state of the frequency drive is restored. See Figure 8-56.<br />

Actual value<br />

Wake up level (param. ID1018)<br />

Time<br />

Output frequency<br />

t < param. ID1017<br />

t < par. ID1017<br />

Sleep level<br />

param. ID1016<br />

Time<br />

Start/Stop status of<br />

the var. speed drive<br />

running<br />

Figure 8-56. Frequency drive sleep function<br />

stop<br />

NX12k56<br />

1019 Wake-up function 57 (2.1.18)<br />

This parameter defines whether the restoration of the Run state occurs when the actual<br />

value signal falls below or exceeds the Wake-up level (par. ID1018). See Figure 8-56<br />

and Figure 8-57 on page 193.<br />

The application 5 has selections 0-1 and application 7 selections 0-3 available.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!