156 Description of Parameters Honeywell<br />

377 AI1 signal selection 234567 (2.2.8, 2.2.3, 2.2.15, 2.2.2.1)<br />

Connect the AI1 signal to the analogue input of your choice with this parameter. For<br />

more information about the TTF programming method, see chapter 6.4.<br />

384 AI1 joystick hysteresis 6 (2.2.2.8)<br />

This parameter defines the joystick hysteresis between 0 and 20 %.<br />

When the joystick or potentiometer control is turned from reverse to forward, the output<br />

frequency falls linearly to the selected minimum frequency (joystick/potentiometer in<br />

middle position) and stays there until the joystick/potentiometer is turned towards the<br />

forward command. It depends on the amount of joystick hysteresis defined with this<br />

parameter, how much the joystick/potentiometer must be turned to start the increase of<br />

the frequency towards the selected maximum frequency.<br />

If the value of this parameter is 0, the frequency starts to increase linearly immediately<br />

when the joystick/potentiometer is turned towards the forward command from the middle<br />

position. When the control is changed from forward to reverse, the frequency follows the<br />

same pattern the other way round. See Figure 8-34.<br />

Frequency reference<br />

Hz<br />

Reference<br />

scaling max<br />

ID304 = 70Hz<br />

A<br />

REVERSE<br />

FORWARD<br />

50% 50%<br />

B<br />

From reverse to forward<br />

Max freq. ID102<br />

= 50Hz<br />

From forward to reverse<br />

Min freq. ID101 =<br />

Ref. scaling min<br />

ID303 = 0Hz<br />

Par. ID321<br />

= 20 %<br />

Joystick hysteresis,<br />

ID384 = 20 %<br />

Par. ID322<br />

= 90 %<br />

Analogue<br />

input (V/mA)<br />

(0-10V/20mA)<br />

Figure 8-34. An example of joystick hysteresis. In this example, the value of par. ID385 (Sleep<br />

limit) = 0<br />

NX12k92<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!