Honeywell Standard Application 17<br />

2.4.4 Output signals (Control keypad: Menu M2 G2.3)<br />

Code Parameter Min Max Unit Default Cust ID Note<br />

P2.3.1<br />

Analogue output 1<br />

TTF programming method<br />

0 A.1 464<br />

signal selection<br />

used. See page 65.<br />

0=Not used<br />

1=Output freq. (0—f max )<br />

2=Freq. reference (0—f max )<br />

3=Motor speed (0—Motor<br />

P2.3.2<br />

Analogue output<br />

nominal speed)<br />

0 8 1 307<br />

function<br />

4=Motor current (0—I nMotor )<br />

5=Motor torque (0—T nMotor )<br />

6=Motor power (0—P nMotor )<br />

7=Motor voltage (0--U nMotor )<br />

8=DC-link volt (0—1000V)<br />

P2.3.3<br />

Analogue output filter<br />

time<br />

0,00 10,00 s 1,00 308 0=No filtering<br />

P2.3.4<br />

Analogue output<br />

0 1 0 309<br />

0=Not inverted<br />

P2.3.5<br />

P2.3.6<br />

P2.3.7<br />

inversion<br />

Analogue output<br />

minimum<br />

Analogue output<br />

scale<br />

Digital output 1<br />

function<br />

0 1 0 310<br />

10 1000 % 100 311<br />

0 16 1 312<br />

1=Inverted<br />

0=0 mA<br />

1=4 mA<br />

0=Not used<br />

1=Ready<br />

2=Run<br />

3=Fault<br />

4=Fault inverted<br />

5=FC overheat warning<br />

6=Ext. fault or warning<br />

7=Ref. fault or warning<br />

8=Warning<br />

9=Reversed<br />

10=Preset speed 1<br />

11=At speed<br />

12=Mot. regulator active<br />

13=OP freq. limit 1 superv.<br />

14=Control place: IO<br />

15=Thermistor fault/warng<br />

16=Fieldbus input data<br />

P2.3.8 RO1 function 0 16 2 313 As parameter 2.3.7<br />

P2.3.9 RO2 function 0 16 3 314 As parameter 2.3.7<br />

P2.3.10<br />

0=No limit<br />

Output frequency<br />

0 2 0 315 1=Low limit supervision<br />

limit 1 supervision<br />

2=High limit supervision<br />

P2.3.11<br />

Output frequency<br />

limit 1; 0,00 320,00 Hz 0,00 316<br />

Supervised value<br />

P2.3.12<br />

Analogue output 2<br />

TTF programming method<br />

0 0.1 471<br />

signal selection<br />

used. See page 65.<br />

P2.3.13<br />

Analogue output 2<br />

function<br />

0 8 4 472 As parameter 2.3.2<br />

P2.3.14<br />

Analogue output 2<br />

filter time<br />

0,00 10,00 s 1,00 473 0=No filtering<br />

P2.3.15<br />

Analogue output 2<br />

0=Not inverted<br />

0 1 0 474<br />

inversion<br />

1=Inverted<br />

P2.3.16<br />

Analogue output 2<br />

0=0 mA<br />

0 1 0 475<br />

minimum<br />

1=4 mA<br />

P2.3.17<br />

Analogue output 2<br />

scaling<br />

10 1000 % 100 476<br />

Table 2-5. Output signals, G2.3<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!