Honeywell Description of Parameters 131<br />

141 AI3 signal selection 567 (2.2.38, 2.2.4.1)<br />

Connect the AI3 signal to the analogue input of your choice with this parameter. For<br />

more information, see Chapter 6.4 “Terminal To Function” (TTF) programming principle.<br />

142 AI3 signal filter time 567 (2.2.41, 2.2.4.2)<br />

When this parameter is given a value greater than 0 the function that filters out<br />

disturbances from the incoming analogue signal is activated.<br />

Long filtering time makes the regulation response slower. See parameter ID324.<br />

143 AI3 signal range 567 (2.2.39, 2.2.4.3)<br />

With this parameter you can select the AI3 signal range.<br />

Applic.<br />

5 6 7<br />

Sel.<br />

0 0…100% 0…100% 0…100%<br />

1 20…100% 20…100% 20…100%<br />

2 –10…+10V Customised<br />

3 Customised<br />

Table 8-6. Selections for parameter ID143<br />

144 AI3 custom setting minimum 67 (2.2.4.4)<br />

145 AI3 custom setting maximum 67 (2.2.4.5)<br />

Set the custom minimum and maximum levels for the AI3 signal within -160…160%.<br />

151 AI3 signal inversion 567 (2.2.40, 2.2.4.6)<br />

0 = No inversion<br />

1 = Signal inverted<br />

152 AI4 signal selection 567 (2.2.42, 2.2.5.1)<br />

See ID141.<br />

153 AI4 filter time 567 (2.2.45, 2.2.5.2)<br />

See ID142.<br />

154 AI4 signal range 567 (2.2.43, 2.2.5.3)<br />

See ID143.<br />

155 AI4 custom setting minimum 67 (2.2.5.3, 2.2.5.4)<br />

156 AI4 custom setting maximum 67 (2.2.5.4, 2.2.5.5)<br />

See ID’s 144 and 145.<br />

162 AI4 signal inversion 567 (2.2.44, 2.2.5.5, 2.2.5.6)<br />

See ID151.<br />

164 Motor control mode 1/2 6 (2.2.7.22)<br />

Contact is open = Motor control mode 1 is selected<br />

Contact is closed = Motor control mode 2 is selected<br />

See parameter ID's 600 and 521.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!