Honeywell Description of Parameters 167<br />

493 Adjust input 6 (2.2.1.4)<br />

With this parameter you can select the signal, according to which the frequency<br />

reference to the motor is fine<br />

adjusted.<br />

0 Not used<br />

1 Analogue input 1<br />

2 Analogue input 2<br />

3 Analogue input 3<br />

4 Analogue input 4<br />

5 Signal from fieldbus<br />

(FBProcess<strong>Data</strong>IN)<br />

44Hz<br />

40Hz<br />

36Hz<br />

f/Hz<br />

Adjusted<br />

Adjust<br />

maximum<br />

ID495 = 10%<br />

Adjust 0 %<br />

Adjust<br />

minimum<br />

ID494 = 10%<br />

Analogue input<br />

NX12K108<br />

Figure 8-41. An example of adjust input<br />

494 Adjust minimum 6 (2.2.1.5)<br />

495 Adjust maximum 6 (2.2.1.6)<br />

These parameters define the minimum and maximum of adjusted signals. See Figure<br />

8-41.<br />

496 Parameter Set 1/Set 2 selection 6 (2.2.7.21)<br />

With this parameter you can select between Parameter Set 1 and Set 2. The input for<br />

this function can be selected from any slot. The procedure of selecting between the sets<br />

is explained in the product's user's manual.<br />

Digital input = FALSE:<br />

- Set 1 is loaded as the active set<br />

Digital input = TRUE:<br />

- The active set is saved to set 1<br />

Note: The parameter values are stored only when selecting P6.3.1 Parameter sets<br />

Store Set 1 or Store Set 2 in System menu or from NCDrive: Drive > Parameter Sets.<br />

498 Start pulse memory 3 (2.2.24)<br />

Giving a value for this parameter determines if the present RUN status is copied when<br />

the control place is changed from A to B or vice versa.<br />

0 = The RUN status is not copied<br />

1 = The RUN status is copied<br />

In order for this parameter to have effect, parameters ID300 and ID3<strong>63</strong> must have been<br />

set the value 3.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!