Cabling and connections 59(110)<br />

6.1.7 Cable and motor insulation checks<br />

1. Motor cable insulation checks<br />

Disconnect the motor cable from terminals U, V and W of the frequency drive and from the<br />

motor. Measure the insulation resistance of the motor cable between each phase conductor as<br />

well as between each phase conductor and the protective ground conductor.<br />

The insulation resistance must be >1MΩ.<br />

2. Mains cable insulation checks<br />

Disconnect the motor cable from terminals L1, L2 and L3 of the frequency drive and from the<br />

mains. Measure the insulation resistance of the motor cable between each phase conductor as<br />

well as between each phase conductor and the protective ground conductor.<br />

The insulation resistance must be >1MΩ.<br />

3. Motor insulation checks<br />

Disconnect the motor cable from the motor and open the bridging connections in the motor<br />

connection box. Measure the insulation resistance of each motor winding. The measurement<br />

voltage must equal at least the motor nominal voltage but not exceed 1000 V. The insulation<br />

resistance must be >1MΩ.<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com<br />

6

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!