36(110) Installation<br />

5.3 Power loss<br />

5.3.1 Power loss as function of switching frequency<br />

If the operator wants to raise the switching frequency of the drive for some reason (typically e.g. in<br />

order to reduce the motor noise), this inevitably affects the power losses and cooling requirements<br />

according to the graphs below.<br />

0.26<br />

0.24<br />

0.21<br />

0.18<br />

0.16<br />

P [HP]<br />

0.13<br />

0.1<br />

0.08<br />

0.05<br />

0.02<br />

0.0<br />

0,00 2,00 4,00 6,00 8,00 10,00 12,00 14,00 16,00<br />

Switching frequency [kHz]<br />

0015NX5 400V 0020NX5 400V 0030NX5 400V 0040NX5 400V<br />

0050NX5 400V 0075NX5 400V<br />

Figure 5-12. Power loss as function of switching frequency; <strong>NXS</strong> 0015…0075 A<br />

1.2<br />

1.07<br />

0.93<br />

0.8<br />

0.67<br />

P [HP]<br />

0.53<br />

0.4<br />

0.26<br />

0.13<br />

0,00<br />

0,00 2,00 4,00 6,00 8,00 10,00 12,00 14,00 16,00<br />

Switching frequency [kHz]<br />

0010NX5 400V 0010NX5 500V 0100NX5 400V 0100NX5 500V<br />

0200NX5 400V 0200NX5 500V<br />

Figure 5-13. Power loss as function of switching frequency; <strong>NXS</strong> 0100…0200 A<br />

Automation and Control Solutions<br />

Honeywell<br />

Honeywell Limited-Honeywell Limitée<br />

1985 Douglas Drive North 35 Dynamic Drive<br />

Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />

MIV 4Z9<br />

www.honeywell.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!