Honeywell Multi-purpose Control Application 73<br />
6.6.3 Basic parameters (Control keypad: Menu M2 G2.1)<br />
Code Parameter Min Max Unit Default Cust ID Note<br />
P2.1.1 Min frequency 0,00 Par. 2.1.2 Hz 0,00 101<br />
P2.1.2 Max frequency Par. 2.1.1 320,00 Hz 50,00 102<br />
P2.1.3 Acceleration time 1 0,1 3000,0 s 3,0 103<br />
P2.1.4 Deceleration time 1 0,1 3000,0 s 3,0 104<br />
P2.1.5 Current limit 0,1 x I H 2 x I H A I L 107<br />
P2.1.6<br />
Nominal voltage of<br />
the motor<br />
180 690 V<br />
NX2: 230V<br />
NX5: 400V<br />
NX6: 690V<br />
110<br />
NOTE: If f max > than the<br />
motor synchronous speed,<br />
check suitability for motor<br />
and drive system<br />
P2.1.7<br />
Nominal frequency<br />
Check the rating plate of<br />
8,00 320,00 Hz 50,00 111<br />
of the motor<br />
the motor<br />
P2.1.8<br />
The default applies for a 4-<br />
Nominal speed of<br />
24 20 000 rpm 1440 112 pole motor and a nominal<br />
the motor<br />
size frequency drive.<br />
P2.1.9<br />
Nominal current of<br />
Check the rating plate of<br />
0,1 x I<br />
the motor<br />
H 2 x I H A I H 113<br />
the motor.<br />
P2.1.10 Motor cosϕ 0,30 1,00 0,85 120<br />
Check the rating plate of<br />
the motor<br />
P2.1.11 I/O Reference 0 15/16 0 117<br />
0=AI1<br />
1=AI2<br />
2=AI1+AI2<br />
3=AI1-AI2<br />
4=AI2-AI1<br />
5=AI1xAI2<br />
6=AI1 Joystick<br />
7=AI2 Joystick<br />
8=Keypad<br />
9=Fieldbus<br />
10=Motor potentiometer<br />
11=AI1, AI2 minimum<br />
12=AI1, AI2 maximum<br />
13=Max frequency<br />
14=AI1/AI2 selection<br />
15=Encoder 1<br />
16=Encoder 2 (NXP only)<br />
0=AI1<br />
1=AI2<br />
2=AI1+AI2<br />
3=AI1-AI2<br />
P2.1.12<br />
Keypad control<br />
4=AI2-AI1<br />
0 9 8 121<br />
reference<br />
5=AI1xAI2<br />
6=AI1 Joystick<br />
7=AI2 Joystick<br />
8=Keypad<br />
9=Fieldbus<br />
P2.1.13<br />
Fieldbus control<br />
reference<br />
0 9 9 122 See par. 2.1.12<br />
P2.1.14<br />
Jogging speed<br />
reference<br />
0,00 Par. 2.1.2 Hz 5,00 124 See ID413.<br />
P2.1.15 Preset speed 1 0,00 Par. 2.1.2 Hz 10,00 105 Multi-step speed 1<br />
P2.1.16 Preset speed 2 0,00 Par. 2.1.2 Hz 15,00 106 Multi-step speed 2<br />
P2.1.17 Preset speed 3 0,00 Par. 2.1.2 Hz 20,00 126 Multi-step speed 3<br />
P2.1.18 Preset speed 4 0,00 Par. 2.1.2 Hz 25,00 127 Multi-step speed 4<br />
P2.1.19 Preset speed 5 0,00 Par. 2.1.2 Hz 30,00 128 Multi-step speed 5<br />
P2.1.20 Preset speed 6 0,00 Par. 2.1.2 Hz 40,00 129 Multi-step speed 6<br />
P2.1.21 Preset speed 7 0,00 Par. 2.1.2 Hz 50,00 130 Multi-step speed 7<br />
Table 6-5. Basic parameters G2.1<br />
Automation and Control Solutions<br />
Honeywell<br />
Honeywell Limited-Honeywell Limitée<br />
1985 Douglas Drive North 35 Dynamic Drive<br />
Golden Valley, MIN 55422 Scarborough, Ontario <strong>63</strong>-<strong>2600</strong>-1<br />
MIV 4Z9<br />
www.honeywell.com