95EN, 85EN, 65ENSystem <strong>Layout</strong>Network 1Wiring Option 1MSNodesMax 1695CONTROLPANEL100m max2 OutputsMSNode1100m max2 Outputs 2 OutputsMSNode2MSNode161kmmaxto furthestMSNodeNetwork 2An MSNode iscapable of driving 4Remote Keypads anda Loudspeaker8 Zones 8 Zones8 Zones5 OutputsNOTE:Do not connect anMSNode to the samenetwork as an ID Nodeor keypad100m max tofurthest keypadMax 48 ZonesNetwork Wiring = 4 CoreEngineer’s keypad(cannot have zonesor outputs)Wiring Option 2Remote Keypads/LEC2sMax 51 Output1 Output1 Output1 Output1 Output100m max tofurthestkeypad/LEC22 Zones 2 ZonesNetwork Wiring = 6 Core2 Zones2 Zones2 Zones(see notebelow)Wiring Option 3MIDNode/IDNode8 OutputsMIDNode/ID NodeMaximum of 120 zoneswith four MIDNodes.Maximum of 40 zoneswith two IDNodes.30 ID ZonesNetwork Wiring = 4 CoreFigure 1. Overview of Network Wiring OptionsNote:• Zones connected to a 9950 or 9951 keypad must be wired as FSL.• Using a Networker Interface Board (NIB) (with power supply) enablesthe maximum distance from a control panel to an MIDNode, IDNode,MSNode or keypad to be increased to 1km.5 of 72