Re-entering Engineering Mode 9500Followed by: Branch 4No of LIMs=6Followed by:Total LIMs=26confirm: yes/no2. EITHER Press NoThe display shows:Review systemconfigurationCheck for system wiring faults, LIM failures etc.See "Branch Configuration"3. OR Press YesThe display shows:Please wait...testing systemFollowed by:Engineer resetall circuits OKFollowed by: 26 July 07:46:37Status:dayYou are now in customer day mode.Re-entering Engineering Mode1. Key in 7890 + Enter.The display shows: Ver 4.2014 FEB 1991Followed by:Do you wantengineer reset?2. Press No.The display shows:3. Press No.The display shows:4. Press No.The display shows:Do you wanttest functions?Do you wantreports?Do you want toprogram the system?5. Open the control panel lid.6. Press Yes.You are now in Engineering Mode.Note:1. If the system is in operation and has to be powered down (battery & mains)for servicing, when powering up, the battery must be connected first.This will16 of 22 496332 Issue 1