11.07.2015 Views

Cooper TP Workshop Manual_Scant:Layout 1 7/8 ... - Cooper Security

Cooper TP Workshop Manual_Scant:Layout 1 7/8 ... - Cooper Security

Cooper TP Workshop Manual_Scant:Layout 1 7/8 ... - Cooper Security

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

95EN, 85EN, 65ENMaximum Cable Distances• Nodes – The distance between a control unit and a Node, or betweenany two Nodes must not exceed 100m. The distance from the controlunit to furthest Node must not exceed 1km. See Figure 8. (You canincrease this distance by adding a NIB (Network Interface Board) tothe system, see page 19.)1 km (Max.)100 metres100 metres 100 metres 100 metresCONTROLPANELDataNetwork4-CoreMSNode MSNode MSNode MSNode MSNodeI/D=1 I/D=2 I/D=3 I/D=4 I/D=16MSNodesIn OutIn OutIn OutIn Out 5 to 16 In OutDaisy-chained Connections1 km (Max.)100 metres 100 metres 100 metres 100 metres 100 metresCONTROLPANELDataNetwork4-CoreMSNode MSNode MSNode MSNode MSNodeI/D=1 I/D=3 I/D=6 I/D=7 I/D=8In OutIn OutIn OutIn OutIn OutMSNodeMSNodeMSNodeMSNodeI/D=2I/D=4I/D=9I/D=10InOutInOutInOutInOutNOTE:The maximum number of devicesthat can be "Star" connected fromthe output of the MSNode or controlpanel is 4.MSNodeI/D=5In OutMSNodeI/D=11In OutStar and Daisy-chained ConnectionsFigure 8. Maximum Distances to MSNodes• Keypads – The distance from a control unit or MSNode to the furthestkeypad on the chain must not exceed 100m (see Figure 9).18 of 72