Rules:Example:1. Infiltration method and required keywords should match.2. SOURCE-BTU/HR, LIGHTING-KW, LIGHTING-W/SQFT, EQUIPMENT-KW andEQUIPi~ENT-W/SQFT all imply energy or fuel use, not necessarilyheat-transferred to the space. -3. The heat transferred to the space is done via the keywordsSOURCE-LATENT, SOURCE-SENSIBLE, LIGHT-TO-SPACE, TASK-LIGHTING-KW,TASK-LT-W/SQFT, EQUIP-LATENT, EQUIP-SENSIBLE.A space is defined as follows. A conditioned zone: air temperature ismaintained at 68'F, floor weight is 75 pounds per square foot, lightingis fluorescent overhead (3 watts/ft 2 ) with some task lighting (300watts), there is a 1-hp motor (1 hp = .745 kW) in the space running at 80per cent efficiency (thus 20 per cent of its energy consumption shows upas heat added to the space), infiltration is 2 air changes per hour, andsix people occupy the space.RM = SPACE-CONDITIONSTEMPERATUREPEOPLE-SCHEDULENUMBER-OF-PEOPLEPEOPLE-HG-LATPEOPLE-HG-SENSLIGHTING-SCHEDULELIGHTI NG-TYPELIGHTING-W/SQFTLIGHT-TO-SPACETASK-LIGHT-SCHEDTASK-LIGHTING-KWEQUIP-SCHEDULEEQUIPMENT-KWEQUIP-SENSIBLEINF-METHODAIR-CHANGES/HRFLOOR-WEIGHTZONE-TYPE= (68)= MANHR= 6= 200.= 250.= HILITE= SUS-FLUOR= 3.= 1.0= LOLITE= 0.3= MOTOR= 0.75= 0.2= AIR-CHANGE= 2.:;; 75.= CONDITIONEDII I. 54 (Revised 5/81)