Note: This keyword should normally be specified for each zone (explicitlyor through a LIKE keyword) to get a more accurate air flow rate for the zone.Optionally, SIZING-OPTION could be specified only for ZONE-TYPE = CONDITIONED(where the user wishes a more accurate air flow rate) and be allowed todefault for ZONE-TYPE = UNCONDITIONED or PLENUM. In this case, the usershould still specify the DESIGN-HEAT-T and DESIGN-COOL-T for ZONE-TYPE =UNCONDITIONED or PLENUM, so that the peak heating and cooling loads ofsurrounding zones are appropriately modified.IV.201.2 (Revised 5/81)