$DEFINE CHARGING SCHEDULES$TANK-OS = DAY-SCHEDULE (1,7)(1)(8,20)(0)(21,24)(1)TANK-WS = WEEK-SCHEDULE (all) TANK-OS ..TANK-SCH = SCHEDULE THRU DEC 31 TANK-WS .•SpaceCoolingLoad3467911$DEFINE USE STRATEGY$COOLERS = LOAD-ASSSIGNMENTTYPE = COOLI NGLOAD-RANGE = 9PLANT-EQUIPMENT = CHILLERNUMBER = 1PLANT-EQUIPMENT = COLD-TANKNUMBER = 1$COLD TANK CAN SUPPLY UP TO 2 MBTUH$LOAD-MANAGEMENTPRED-LOAD-RANGE = 999LOAD-ASSIGNMENT = (DEFAULT,COOLERS,DEFAULT)A typical scenario for nighttime operation is shown be 1 ow.TankChargingRateTotalLoadChillerOutputTankReceivesTankDelivers Remarks3 6 6 3 0 Rule 13 7 7 3 0 Rule 13 9 7 1 0 Ru les 1 and3 10 7 0 0 Rules 1 and3 12 7 0 2 Rules 1 and3 14 7 0 2 Overload by 2 MBtuh222Now let's assume that the user wants to charge the tank atnight and base-load it during the day. The user might redefinethe LOAD-ASSIGNMENT instruction as follows:COOLERS = LOAD-ASSIGNMENTTYPE = COOLI NGLOAD-RANGE = 9PLANT-EQUIPMENT = COLD-TANKNUMBER = 1PLANT-EQUIPMENT = CHILLERNUMBER = 1 ..V.78 (Revi sed 5/81)