HeatingCBF ~EIRT ~QE ~COIL-BF * COIL-BF-FT(EWB,ODB) * COIL-BF-FCFM(CFMPLR),COOLING-EIR * COOL-EIR-FT(EWB,ODB) * COOL-EIR-FPLR(PLR),CAPT * EIRT'1. Electric resistance (HEAT-SOURCE ~ ELECTRIC)CAPT ~QE ~HEATING-CAPACITYHeating load2. Electric heat pump (HEAT-SOURCE ~ HEAT-PUMP)CAPT ~EIRT ~HEATING-CAPACITY * HEAT-CAP-FT(ODB,EDB)HEATING-EIR * HEAT-EIR-FT(ODB,EDB) * HEAT-EIR-FPLR(PLR)QE ~ CAPT ~ EIR T •3. Gas or oil furnace (HEAT-SOURCE ~ GAS-FURNACE or OIL-FURNACE)CAPT ~HIRT ~QE ~HEATING-CAPACITYFURNACE-HIR * FURNACE-HIR-FPLR(PLR)CAPT * HIRT'Additional modifier functions are available to allow adjustment for flowrates other than those for which rating information is published(RATED-CCAP-FCFM, RATED-SH-FCFM, RATED-CEIR-FCFM, RATED-HCAP-FCFM,RATED-HEIR-FCFM), for defrosting heat pumps (DEFROST-DEGRADE), and furnaceinduced losses (FURNACE-OFF-LOSS).IV.239 (Revised 5/81)