INPUT SYSTEMSCOOL-CAP-CURVE = CURVE-FITTYPE = BI-QUADRATICDATA = (67, 95, 1.0) MRI POINT$(72, 95, 1.079)(62, 95, 0.905)(72, 105, 1.032)(67,105,0.952)(62, 105, 0.841)(72, 115, 0.984)(67, 115, 0.873)(62, 115, 0.778)(72, 85, 1.095)(67, 85, 1.032)(62, 85, 0.952)PACKAGED-SYS = SYSTEM-EQUIPMENTCOOLING-CAPACITY = 150000COOL-CAP-FT = COOL-CAP-CURVEExample 2:END ..Figure IV.20 is a sample output of the program when DIAGNOSTIC = COMMENTS.Specification of CoefficientsIn Table V.6 of the PLANT Chapter, the user finds that the default coefficientsfor the curve that expresses the exhaust heat of a gas turbine, as afunction of ambient air temperature, (GTURB-EXH-FT), are 0.018226, 0.000029,and 0.0. The user's manufacturer's data indicate that for the turbine he ismodeling, it would be more accurate to change the first coefficient to0.022105. As the third coefficient is zero, the curve may be represented inthe form z = a + bx. The input might look like:INPUT PLANTG-EXH-H = CURVE-FITTYPE = LINEARCOEFFICIENTS = (0.022105, 0.000029)EQUIPMENT-QUADGTURB-EXH-FT = G-EXH-HENDIV.185 (Revised 5/81)