air ducts to the ZONE. If the user does not specify a HEAT-TEMP-SCHfor a ZONE, it will not be heated but it will be cooled (assuming atleast one COOL-TEMP-SCH was specified and the baseboard heaters, ifpresent, do not have BASEBOARD-CTRL = OUTDOOR-RESET).(7) Specify THERMOSTAT-TYPE = PROPORTIONAL in the ZONE-CONTROLsubcommand (or let it default).(8) The desired control strategy for the system has now been specified.To complete the input, specify values for the other keywords thatare appropriate to the SYSTEM-TYPE being simulated, or allow thesekeywords to default. This example is the tenth strategy in TableI V. 26 •IV.125 (Revised 5/81)