TOP-FLOOR = SPACEFLOOR INTERIOR-WALLNEXT-TO = MID-FLOORSMID-FLOORS = SPACEMULTIPLIER = 7GROUND-FLOOR = SPACE~FLOOROF TOP-FLOOR~~FLOORS 2 THRU 8~CEILING = INTERIOR-WALL ~CEILING OF GROUND-FLOOR$NEXT-TO = MID-FLOORSThe program more closely simulates what is shown inFig. I 11. 22.TOP-FLOOR2 I 3 I 4 I 5 I 6 I 7 I 8GROUND-FLOOR- ",. ",~_1111=U.U,:_fi71,::'I-U.l.l=I~-~"-!.UJ~IIII=1I1' 11"1I=1~=.w.I::-J. ll'iI~Il: = :-111,1~ "TI="Fig. II1.22.Actual simulation, incorrectly showing allfloors (2 through 8) NEXT-TO both TOP-FLOORand GROUND-FLOOR.That is, floors 2 through 8 can be thought of thermally asoperating in parallel between GROUND-FLOOR and TOP-FLOORrather than in series. This mayor may not be important tothe user; only the user can decide. This may not be asserious as assuming that floors 2 through 8 are thermallyidentical, especially where internal loads are concerned.A more appropriate application of the keyword MULTIPLIER ina SPACE instruction is shown in Fig. II1.23.II 1.95 (Revised 5/81)