STURB-PRESSTURB-SPEEDSTURB-TSTURB-WTR-RETURNSTM-PRESSTM-SATURATI ON-TSolarMIN-SOL-COOL-TMIN-SOL-HEAT-TMIN-SOL-PROCESS-Tspecifies the pressure of the steam entering thesteam-turbine generator. If no entry is made for thiskeyword, the value of STURB-PRES will default to STM-PRESif STM-PRES is less than ISO psig or to ISO psig ifSTM-PRES is greater than or equal to ISO psig.specifies the speed (rpm) of the steam turbine generatorwhen it is operating at nominal capacity.specifies the temperature of the steam entering thesteam-turbine generator. If no entry is made for thiskeyword, the value of STURB-T will default toSTM-SATURATION-T plus 12SoF.is the ratio of the condensate-feedwater flow to thenominal steam rate for the steam turbine generator(lb/lb).specifies the boiler steam pressure. If no entry ismade, the value of STM-PRES will default to IS psigunless a two-stage absorption cooler or steam-turbinegenerator is specified. In this case, the program will~se a default value of ISO psig. The value is used tocalculate STM-SATURATION-T and STURB-PRES if these valuesare not input.specifies the saturation temperature of boiler steam.Any value entered within the range will be used by theprogram, even if inconsistent with values entered forkeyword STM-PRES. If no entry is made, the program willcalculate STM-SATURATION-T for saturated steam atSTM-PRES. This value is used by the diesel and gasturbine simulation routines to calculate the amount ofheat recoverable from exhaust gas.specifies the mlnlmum solar storage tank temperature forsolar space cooling. Solar space cooling can only beaccomplished through the use of the HEAT-RECOVERYinstructions.specifies the mlnlmum solar storage tank temperaturerequired for space heating through a HEAT-RECOVERYinstruction. Solar space heating which is accomplishedin the solar simulation is unaffected by thisspecification.specifies the minimum solar storage tank temperaturerequired for a process or domestic hot water through aHEAT-RECOVERY instruction.V.32 (Revised S/B1)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!