TABLE IV.39SYSTEM-EQUIPMENT DEFAULT CURVESEquations are assumed to take the form:1 i near t or z ." a + bxbi-linear, or z ." a + bx + dyquadratic, or z ." a + bx + cx2bi-quadratic, or z = a + bx + cx2 + dy + eyl + fxycubic, or z = a + bx + cx2 + dx 3DefaultDefault Curve CoefficientsCurveIndependent ApplicableU-name Keyword Variable(s)* SYSTEM-TYPE a b c d e fSOL-Cl CooL-CAP-FT WB/OOB RESYS 0.59815404 0.01329987 0.0 -0.00514995 0.0 0.0SOL-C2 COOL-CAP-FT WB/OOB PTAC 0.41905 0.01715 0.0 -0.00598 0.0 0.0SOL-C3 COOL-CAP-FT WB/OOB PSZ,PMZS,PVAVS 0.418943 0.017421 0.0 -0.00617 0.0 0.0SOL-C5 COOL-CAP-FT WB/WT HP 0.56735 0.0137 0.0 -0.00647 0.0 0.0SOL-Cl COOL-CAP-FT WB/OB Builtup -2.733941 0.0520215 0.0 0.00310625 0.0 0.0SOL-CI0 COOL-CAP-FT WB/OB TPFC,FPFC -2.95444 0.05372 0.0 0.00444 0.0 0.0SOL-Cll CooL-EJR-FT WB/OOB RESYS 0.49957503 -0.00765992 0.0 0.01066989 0.0 0.0SOL-CI2 COOL-EJR-FT WB/OOB PTAC 0.282094 -0.005832 0.0 0.01167 0.0 0.0~SOL-CI3 CooL-EJR-FT WB/OOB PSZ,PMZS,PVAVS 0.282094 -0.005832 0.0 0.01167 0.0 0.0