InputRangeKeyword Abbrev. User Input Desc. Default Min. Max.MAX-GTU RB-E XH = lb/kW 40. 0.+ 100.(Note 1)STURB-EXH-PRES psig -12.7 -15.(Note 4)1000.STURB-PRES psig 15. -15.(Note 4)700.STURB-SPEED = rpm 5000. 0.+ 1. x10 4STURB-T of 378.7 212.(Note 4)1000.STURB-WTR-RETURN = lb/lb 0.97 0.+ l.STM-PRES = psig 15. -15. 700.(Note 4)STM-SATURATION-T =of 253.7 212. 500.(Note 4)SolarMIN-SOL-COOL-T of 180. 80. 212.MIN-SOL-HEAT-T of 100. 60. 2l2.MIN-SOL-PROCESS-T =of 140. 60. 2l2.PumpsCCIRC-DESIGN-T-DROP =of 10. 0.+ 20.CCIRC-HEAD ft 60. O. 100.CCIRC-IMPELLER-EFF fraction 0.77 0.+ l.CCIRC-LOSS = ratio 0.01 O. l.CCIRC-MOTOR-EFF = fraction 0.9 0.+ l.HCIRC-DESIGN-T-DROP =of 30. 0.+ 100.HCIRC-HEAD ft 60. O. 100.HCIRC-IMPELLER-EFF fraction 0.77 0.+ l.HCIRC-LOSS ratio 0.01 O. l.HCIRC-MOTOR-EFF fraction 0.9 0.+ l.Notes:l. A minimum of "0.+" means· that any positive number in the range is acceptable, butzero itself is not, as the value may be used as a divisor.4. See keyword description for alternative default value.V.37 (Revised 5/81)