U-name= SYSTEM-FANS or S-FANS (User Worksheet)InputRangeKeyword Abbrev. User Input Desc. Default Min. Max.LIKE = U-nameFAN-SCHEDULE F-SCH = U-name Note 1FAN-CONTROL F-C = code-word Note 2SUPPLY-DELTA-T SUP-D-T =of Note 3 O. 30.SUPPLY-KW S-KW = kWI s td cfm Note 3 O. .01SUPPLY-STATIC S-S = inches W.G. Note 3 O. 15.SUPPLY-MECH-EFF S-M-E = fraction 0.1 1.SUPPLY-EFF S-E = fraction Note 3 0.1 1.MOTOR-PLACEMENT M-P = code-word Note 4FAN-PLACEMENT F-P = code-word Note 5RETURN-DEL TA-T RET-D-T =OF Note 6 O. 30.RETURN-KW R-KW = kW/cfm Note 6 O. .01RETURN-STATIC R-S = inches W.G. Note 6 O. 10.RETURN-EFF R-E = fraction Note 6 0.1 1.MAX-FAN-RATIO MAX-F-R = number Note 2 1. 1.5MIN-FAN-RATIO MIN-F-R = fraction Note 2 0.1 1.LOW-SPEED-RATIOS L-S-R = list of Note 7four valuesO. 1.NIGHT-CYCLE-CTRL N-C-C = code-word Note 2FAN-EIR-FPLR F-E-FPLR = U-name of alinear,quadratic,or cubicCURVE-FIT1) If no data entry is made for this keyword, the program assumes that thefan(s) are always available when needed, i.e., THRU DEC 31 (ALL) (1,24)(1).2) See the proper Applicability Table (Sec. B.4 of this chapter) forapplicability or the default value. If the keyword is not listed in thetable, it is not applicable to the system being specified.IV.229 (Revised 5/81)