DDE-2Coolingc;- SetpointThermo~tatSetpointOOE-2T/':rottlingRange00E-2He6tingSetpoint"70 75 so85Fig. IV.13.PROPORTIONAL heating/cooling controlled in sequence (no deadband)from single setpoint with seasonal temperature reset.System heating and/or cooling capability may be deactivatedseasonally, although both heating and cooling are often available, atleast during the intermediate seasons. The following is an example ofdata input to simulate the thermostat operation shown in Fig. IV.13 for asystem that has cooling equipment shut off in winter and heatingequipment shut-off in summer. The values entered for COOL-TEMP-SCHduring the month that cooling is shut off, and for HEAT-TEMP-SCH duringthe months that heating is shut off, have no significance. Note thatwhen simulating a constant-volume reheat type system, heating is requiredfor temperature control, even in summer, and should not be shut-off.H-SCH6 = SCHEDULE THRU MAY 15 (ALL) (1,24) (67)THRU NOV 15 (ALL) (1,24) (77 )THRU DEC 31 (ALL) (1,24 ) (67)C-SCH6 = SCHEDULE THRU MAY 15 (ALL) (1,24) (69)THRU NOV 15 (ALL) (1,24) (79)THRU DEC 31 (ALL) (1,24 ) (69)IV.lll (Revised 5/81)