REPORT SS-H - SYSTEM MONTHLY LOADS SUMMARYIn this monthly load summary the name of the HVAC system is given in thetitle (SYST-l). Found in this report is the fan energy requirement for theHVAC system.1. Under FAN ELEC is shown the total and maximum hourly electricalconsumption of the supply, return, exhaust, and outside fans.2. Under FUEL HEAT is presented the total oil and gas consumed in Btuequivalents by the system. This will be zero unless the user has made atleast one of the heat sources OIL-FURNACE or GAS-FURNACE.3. For ELEC HEAT the data describe the electrical consumption for heating.This will include electric baseboards and reheat coils as well as theelectrical load attributable to the heating cycle of a heat pump.4. ELEC COOL shows the electrical consumption and hourly maxima for cooling.VII.81