___ ~O~KING PERIOD_____ OFF-HRCOOL-1""UIIht~:~bn,...__- _ _,.-Cooling ....s-'/S"PO'"' ,',,''1'/Hei.tl~;i~oolln9 - ---,.----------.,..____.f._________ ~,'---_I 00" ,lIedt I,' HeatingAddition ,~ Setpoint! .,'HEAT-HAl70 75 so asZone Temperat~re ·FFig. IV.12.PROPORTIONAL heating/cooling thermostat operation (with deadband)and off-hour offset.Case 7PROPORTIONAL Heating/Cooling Controlled in Sequence (nodeadband) from Single Setpoint with Seasonal Temperature ResetFigure IV.13 depicts this mode of operation, which differs from thatshown in Case 5 primarily in that there is no deadband. Note that <strong>DOE</strong>-2requires the specification of separate heating and cooling set points,despite the fact that the thermostat installed in this case, has only oneset point. These set points must be separated by exactly oneTHROTTLING-RANGE, to avoid erroneous simulation of a deadband. (Theactual thermostat has a proportional band that is twice the simulatedTHROTTLING-RANGE.) The actual thermostat set point is at the point wherethe heating and cooling throttling ranges meet.IV.170 (Revised 5/81)