Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10<br />

hb1<br />

2.5<br />

3-10-6 Settings: Heater Short Alarm<br />

9. For this example, set 2.5. To return to the operation level, press the O<br />

Key for less than one second.<br />

To activate the HS alarm, set the HS Alarm Use parameter to ON in the<br />

advanced function setting level and set the HS Alarm 1 and HS Alarm 2<br />

parameters in the adjustment level.<br />

Operating Procedure This procedure sets the HS Alarm 1 parameter to 2.5.<br />

■ Moving to the Advanced Function Setting Level<br />

The HS Alarm Use parameter setting is already ON by default, so set the HS<br />

Alarm 1 parameter.<br />

Operation Level 1. Move to the advanced function setting level.<br />

C<br />

PV/SP<br />

25.0<br />

100.0<br />

Press the O Key for at least three seconds to move from the operation<br />

level to the initial setting level.<br />

Initial Setting Level 2. Select Move to Advanced Function Setting Level by pressing the M Key.<br />

Input Type<br />

(For details on moving between levels, refer to 4-8 Moving to the Advanced<br />

Function Setting Level.)<br />

in-t 5<br />

Initial Setting Level 3. Press the D Key to enter the password (−169), and move from the initial<br />

setting level to the advanced function setting level.<br />

amov<br />

-169<br />

Advanced Function Setting Level The top parameter in the advanced function setting level is displayed.<br />

init<br />

off<br />

hsu on<br />

Move to the<br />

Advanced<br />

Function<br />

Setting Level<br />

HS Alarm<br />

Use<br />

4. Select the HS Alarm Use parameter by pressing the M Key.<br />

Check that this parameter is set to ON (the default).<br />

Next, set the HS Alarm 1 parameter.<br />

79