Thermocouple Calibration (Thermocouple/Resistance Thermometer Input) Section 6-3<br />

288<br />

c400 4<br />

29be<br />

bias<br />

35b8<br />

str no<br />

8. Press the M Key. The display changes as shown on the left.<br />

Set the STV to 400 mV.<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

9. When the M Key is pressed, the status changes as shown to the left.<br />

10. Change the wiring as follows:<br />

Short-circuit<br />

Open in non-connected state<br />

STV<br />

DMM<br />

Zero<br />

controller<br />

OUTPUT INPUT<br />

Disconnect the STV to enable the thermocouple of the cold junction compensator.<br />

When doing this, be sure to disconnect the wiring on the STV<br />

side.<br />

11. Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

12. When the M Key is pressed, the status changes as shown to the left.<br />

The data to be temporarily registered is not displayed if it is not complete.<br />

Press the U Key. The No. 2 display changes to yes. Release the key and<br />

wait two seconds or press the M Key. This stores the temporarily registered<br />

calibration data to EEPROM. To cancel the saving of temporarily<br />

registered calibration data to EEPROM, press the M Key (while no is displayed<br />

in the No. 2 display) without pressing the U Key.<br />

13. The calibration mode is ended by turning the power OFF.<br />

For <strong>Controllers</strong> that have a transfer output (<strong>E5AN</strong>/EN-H@@F), transfer<br />

output calibration continues to be performed. For details on the settings,<br />

refer to 6-6 Calibrating the Transfer Output on page 292.<br />

−<br />

+<br />

Compensating conductor of currently<br />

selected thermocouple<br />

Use K thermocouple compensating<br />

conductor for E, R, S, B, W and PLII<br />

thermocouple.