Operation Level Section 5-3<br />

See<br />

188<br />

■ Related Parameters<br />

Input type: Page 224, Scaling upper limit, Scaling lower limit, Decimal point:<br />

Page 226, Alarm 2 type: Page 233 (initial setting level), Standby sequence<br />

reset: Page 244, Auxiliary output * open in alarm: Page 245, Alarm 2 hysteresis:<br />

Page 233, Alarm 2 latch: Page 250 (advanced function setting level)<br />

Bank * alarm value upper limit 2, Bank * alarm value lower limit 2 (bank setting<br />

level): Page 213<br />

al3h Alarm Value Upper Limit 3 Alarm 3 must be assigned.<br />

al3l Alarm Value Lower Limit 3<br />

Function<br />

Setting<br />

See<br />

o MV Monitor (Heating)<br />

Function<br />

Monitor<br />

The alarm 3 type must not be 1, 4, or<br />

5.<br />

These parameters independently set the alarm value upper and lower limits<br />

when the mode for setting the upper and lower limits is selected for the Alarm<br />

3 Type parameter (initial setting level).<br />

This parameter sets the upper and lower limit values of alarm 3.<br />

During temperature input, the decimal point position depends on the currently<br />

selected sensor, and during analog input it depends on the Decimal<br />

Point parameter setting.<br />

The set value is saved in the Alarm Value Upper Limit 3 and Alarm Value<br />

Lower Limit 3 parameters in the current bank.<br />

Setting range Unit Default<br />

−1999 to 9999 EU 0<br />

■ Related Parameters<br />

Input type: Page 224, Scaling upper limit, Scaling lower limit, Decimal point:<br />

Page 226, Alarm 3 type: Page 234 (initial setting level), Standby sequence<br />

reset: Page 244, Auxiliary output * open in alarm: Page 245, Alarm 3 hysteresis:<br />

Page 233, Alarm 3 latch: Page 250 (advanced function setting level)<br />

Bank * alarm value upper limit 3, Bank * alarm value lower limit 3 (bank setting<br />

level): Page 214<br />

The MV Display parameter must be<br />

set to ON.<br />

This parameter is used to check the manipulated variable for the heating control<br />

output during operation.<br />

This parameter cannot be set.<br />

During standard control, the manipulated variable is monitored. During<br />

heating/cooling control, the manipulated variables on the control output<br />

(heating) is monitored.<br />

The default is OFF and the manipulated variable is not displayed.<br />

Control Monitor range Unit<br />

Standard −5.0 to 105.0 %<br />

Heating/cooling 0.0 to 105.0 %