Moving to the Advanced Function Setting Level Section 4-8<br />

Alarms during SP<br />

Ramp Operation<br />

104<br />

The operation of alarms during SP ramp operation depends on whether<br />

alarms are set to be based on the ramp set point or the target set point (refer<br />

to the following diagrams). The set point to be used is set in the Alarm SP<br />

Selection parameter.<br />

Alarm SP Selection = Ramp SP (Alarm Type: 1 (Upper/Lower Limits))<br />

Temperature<br />

Alarm SP Selection = Target SP (Alarm Type: 1 (Upper/Lower Limits))<br />

Temperature<br />

Alarm output ON<br />

Alarm output ON<br />

4-8 Moving to the Advanced Function Setting Level<br />

Use the following procedure to move to the advanced function setting level.<br />

1,2,3... 1. Press the O and M Keys simultaneously for at least three seconds in operation<br />

level.<br />

Note The key pressing time can be changed in the Move to Protect Level<br />

Time parameter (advanced function setting level).<br />

Time<br />

Alarm output ON<br />

Alarm output ON<br />

Protect Level 2. The Controller moves to the protect level, and the Operation/Adjustment<br />

Operation/Adjustment<br />

Protect<br />

Protect parameter is displayed.<br />

oapt 0<br />

icpt 0<br />

icpt 0<br />

Initial Setting/<br />

Communications<br />

Protect<br />

Time<br />

3. Press the M Key once to move to the Initial Setting/Communications Protect<br />

parameter.<br />

4. Set the set value to 0. The default setting is 0 (possible to reach).