Adjustment Level Section 5-4<br />

l.adj Adjustment Level Display<br />

Function<br />

at AT Execute/Cancel<br />

Function<br />

Operation<br />

See<br />

192<br />

This parameter is displayed after moving to the adjustment level.<br />

When a logic operation is set, a period "." will be displayed on the No. 2. display.<br />

This parameter indicates that the adjustment level has been entered.<br />

(The Adjustment Level parameter will not be displayed again even if the<br />

M Key is pressed in the adjustment level to scroll through the parameters.)<br />

The ramp must be in operation, and<br />

2-PID control must be used. Event<br />

Input Assignments 1 to 4 parameters<br />

must be other than 100% or 40% AT<br />

Execute/Cancel.<br />

This parameter executes auto-tuning (AT).<br />

The MV is forcibly increased and decreased around the set point to find<br />

the characteristics of the control object. From the results, the PID constants<br />

are automatically set in the Proportional Band (P), Integral Time (I),<br />

and Derivative Time (D) parameters.<br />

Both 100% AT and 40% AT are supported for AT.<br />

Only 100% AT can be executed for heating/cooling control and positionproportional<br />

floating control.<br />

This parameter will not be displayed when either 100% or 40% AT execute/cancel<br />

is set to be executed using an event input.<br />

Setting rage Default<br />

OFF: AT Cancel<br />

OFF<br />

AT-2: 100%AT Execute<br />

AT-1: 40%AT Execute<br />

This parameter is normally off. Press the U Key and select at-2 or at-<br />

1 to execute AT. AT cannot be executed when control is stopped or during<br />

ON/OFF control.<br />

When AT execution ends, the parameter setting automatically returns to<br />

off.<br />

■ Related Parameters<br />

PID * proportional band, PID * Integral time, PID * Derivative time (PID setting<br />

level): Page 217<br />

PID ON/OFF (initial setting level): Page 228