Logic Operations Section 4-25<br />

Operating Procedure This procedure outputs alarm 1 status to auxiliary output 1 during operation<br />

(RUN). A library object is used to make the setting.<br />

Alarm 1 RUN/STOP Work bit 1<br />

Always OFF Always OFF<br />

1. Select Logic Operation Editor from the CX-Thermo<br />

tree, and click the Start Button.<br />

2. Click the Import of Library Button.<br />

3. Select Library 1 from the library list, and then click the<br />

OK Button.<br />

Confirm the following settings, and then click the OK<br />

Button.<br />

Work bit 1 operation type: Operation 1<br />

Work bit 1 input assignment A = 7: Alarm 1<br />

Work bit 1 input assignment B = 19: Invert for RUN/<br />

STOP<br />

Work bit 1 input assignment C = 0: Always OFF<br />

Work bit 1 input assignment D = 0: Always OFF<br />

Auxiliary output 1 = Work bit 1<br />

4. Closing the Logic Operation Editor Dialog Box<br />

Click the Close Button.<br />

This completes the procedure for setting parameters<br />

using the CX-Thermo. Transfer the settings to the Controller<br />

to set the Controller. Refer to CX-Thermo help for the<br />

procedure to transfer the settings.<br />