05.03.2013 Views

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

PID Setting Level Section 5-6<br />

*.p PID * Proportional Band<br />

*.i PID * Integral Time 2-PID control must be used.<br />

*.d PID * Derivative Time (*: 1 to 8)<br />

Function<br />

Setting<br />

See<br />

These parameters set the PID constants for each PID set. When AT and ST<br />

are executed, the parameters are set automatically.<br />

P action: For the P action, the MV is proportional to the derivative.<br />

I action: For the I action, an output is produced that is proportional to the time<br />

integral of the derivative. An offset normally occurs with the proportional<br />

action, so the proportional action is used in combination with the integral<br />

action. As time passes, this offset disappears and the control temperature<br />

comes to match the set point.<br />

D action: For the D action, an output is produced that is proportional to the time<br />

derivative of the input. Because the proportional action and integral<br />

action correct for errors in the control result, the control system will be<br />

slow to respond to sudden changes in temperature. The derivative<br />

action performs a corrective action by increasing the MV in proportion to<br />

the slope of the temperature change.<br />

Parameter Setting range Unit Default<br />

Proportional Temperature: 0.1 to 3,240.0 °C or °F 8.0<br />

Band<br />

Analog: 0.1 to 999.9 %FS 10.0<br />

Integral Time Standard/heating and cooling,<br />

position proportional (closed): 0.0<br />

to 3,240.0<br />

Position proportional (floating): 0.1<br />

to 3,240.0<br />

s 233.0<br />

Derivative Time 0.0 to 3240.0 s 40.0<br />

Note If the settings for RT (robust tuning) are changed, the P (proportional<br />

band), I (integral time), and D (derivative time) will be initialized.<br />

■ Related Parameters<br />

AT execute/cancel (adjustment level): Page 192<br />

*.olh PID * MV Upper Limit 2-PID control must be used.<br />

The ST parameter must be set to<br />

*.oll<br />

Function<br />

PID * MV Lower Limit<br />

(*: 1 to 8)<br />

OFF.<br />

Closed control must be used (for<br />

position proportional models).<br />

These parameters set the MV upper and lower limits for each PID set.<br />

The MV Upper Limit and MV Lower Limit parameters set the upper and<br />

lower limits of the manipulated variable. When the calculated manipulated<br />

variable exceeds the upper or lower limit value, the upper or lower limit<br />

value will be the output level.<br />

MV limits do not operate when floating control is used with models that<br />

support position-proportional control, so these parameters are disabled.<br />

217

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!