Error Displays<br />

304<br />

Appendix<br />

When an error occurs, the error contents are shown on the No. 1 or the No. 2 display.<br />

This section describes how to check error codes on the display, and the actions to be taken to remedy the<br />

problems.<br />

s.err<br />

Input Error<br />

Meaning<br />

The input value has exceeded the control range. (See note.)<br />

Note Control Range<br />

Resistance thermometer, thermocouple input: Temperature setting lower limit −20°C to temperature<br />

setting upper limit +20°C<br />

(Temperature setting lower limit −40°F to temperature<br />

setting upper limit +40°F)<br />

Analog input −5% to +105% of scaling range<br />

Action<br />

Check the wiring of inputs for miswiring, disconnections, and short-circuits and check the input type.<br />

If no abnormality is found in the wiring and input type, turn the power OFF then back ON again.<br />

If the display remains the same, the Controller must be replaced. If the display is restored, then the probable<br />

cause is electrical noise affecting the control system. Check for electrical noise.<br />

Note With resistance thermometer input, a break in the A, B, or B’ line is regarded as a disconnection.<br />

Operation at Error<br />

After an error occurs, the error is displayed and the alarm outputs function as if the upper limit has been<br />

exceeded.<br />

When the Input Error Output parameter in the advanced function setting level is set to ON, the output assigned<br />

to the alarm 1 function turns ON whenever an input error occurs.<br />

An error message is displayed when the PV, PV/SP, or PV/MV is displayed.<br />

Note The control output turns OFF. When the manual MV, MV at stop, or MV at PV error is set, however the<br />

control output corresponds to the set value.<br />

[[[[<br />

]]]]<br />

Display Range Exceeded<br />

Meaning<br />

Though this is not an error, it is displayed if the process value exceeds the display range when the control<br />

range is larger than the display range.<br />

The display ranges are shown below (with decimal points omitted).<br />

When less than −19,999 [[[[<br />

When more than 32,400 ]]]]