Advanced Function Setting Level Section 5-10<br />

pidi<br />

pidh<br />

Function<br />

Setting<br />

See<br />

p-db PV Dead Band<br />

Function<br />

Setting<br />

See<br />

PID Set Automatic Selection Data<br />

PID Set Automatic Selection Hysteresis<br />

The control must be set to 2-PID<br />

control.<br />

This parameter provides the data for automatic selection of the PID set.<br />

The PID set number to be used is automatically selected according to the<br />

data set in the PID Set Automatic Selection Data parameter. The selection<br />

range is specified in the PID Set Automatic Selection Range Upper<br />

Limit parameter.<br />

The PID Set Automatic Selection Hysteresis parameter is used to set the<br />

hysteresis to prevent chattering when the PID set is changed.<br />

Parameter Setting range Unit Default<br />

PID Set Automatic Selec- pv: Process value --- PV<br />

tion Data<br />

dv: Deviation<br />

sp: Set point<br />

PID Set Automatic Selection<br />

Hysteresis<br />

0.10 to 99.99 %FS 0.50<br />

■ Related Parameters<br />

PID set automatic selection range upper limit (PID setting level): Page 269<br />

Bank * PID set No. (bank setting level): Page 210<br />

Position-proportional control must be<br />

supported.<br />

For position-proportional models, control is executed with the process<br />

value equal to the set point when the process value is within the PV dead<br />

band.<br />

This function prevents unnecessary outputs when the process value<br />

approaches the set point.<br />

Setting range Unit Default<br />

0 to 32400 EU 0.0<br />

■ Related Parameters<br />

Closed/floating (initial setting level): Page 239<br />

Motor calibration (initial setting level): Page 240<br />

Travel time (initial setting level): Page 240<br />

Position proportional dead band (adjustment level): Page 207<br />

Open/close hysteresis (adjustment level): Page 207<br />

269