Setting the PF Key Section 4-20<br />

4-20 Setting the PF Key<br />

4-20-1 PF Setting (Function Key)<br />

PF Setting Pressing the PF Key for at least one second executes the operation set<br />

pf<br />

a-m<br />

in the PF Setting parameter (<strong>E5AN</strong>/EN-H only).<br />

148<br />

Set value Symbol Setting Function<br />

OFF off Disabled Does not operate as a function key.<br />

RUN run RUN Specifies RUN status.<br />

STOP stop STOP Specifies STOP status.<br />

R-S r-s RUN/STOP reverse Specifies reversing the RUN/STOP opera-<br />

operation<br />

tion status.<br />

AT-2 at-2 100% AT<br />

Specifies reversing the 100% AT Execute/<br />

Execute/Cancel Cancel status. (See note 1.)<br />

AT-1 at-1 40% AT<br />

Specifies reversing the 40% AT Execute/<br />

Execute/Cancel Cancel status. (See notes 1 and 2.)<br />

LAT lat Alarm Latch Cancel Specifies canceling all alarm latches. (See<br />

note 3.)<br />

A-M a-m Auto/<strong>Manual</strong> Specifies reversing the Auto/<strong>Manual</strong> status.<br />

(See note 4.)<br />

PFDP pfdp Monitor/Setting Item Specifies the monitor/setting item display.<br />

Select the monitor setting item according to<br />

the Monitor/Setting Item 1 to 5 parameters<br />

(advanced function setting level).<br />

BANK bank Bank Selection Specifies switching to the bank number + 1.<br />

Note (1) When AT cancel is specified, it means that AT is cancelled regardless of<br />

whether the AT currently being executed is 100% AT or 40% AT.<br />

(2) The setting of AT-1 will be ignored for heating/cooling control or for position-proportional<br />

floating control.<br />

(3) Alarms 1 to 3, heater burnout, HS alarms, and heater overcurrent latches<br />

are cancelled.<br />

(4) For details on auto/manual operations using the PF Key, refer to 4-13 Performing<br />

<strong>Manual</strong> Control.<br />

(5) Pressing the PF Key for at least one second executes operation according<br />

to the set value. When the Monitor/Setting Item parameter is selected,<br />

however, the display is changed in order from Monitor/Setting Item 1 to 5<br />

each time the key is pressed.<br />

(6) This function is enabled when PF Key Protect is OFF.<br />

Monitor/Setting Item<br />

Monitor/Setting Item 1 Setting the PF Setting parameter to the Monitor/Setting Item makes it possi-<br />

Item 5 pfd1<br />

pfd5 1<br />

0<br />

ble to display monitor/setting items using the function key. The following<br />

table shows the details of the settings. For setting (monitor) ranges, refer to<br />

the applicable parameter.