Advanced Function Setting Level Section 5-10<br />

Setting<br />

See<br />

The output is turned OFF when switching to the initial setting level, communications<br />

setting level, advanced function setting level, or calibration<br />

level.<br />

If an auxiliary output is set to close in alarm, the output is kept closed. If it<br />

is set to open in alarm, it is kept open.<br />

Setting range Default<br />

on: Enabled, off: Disabled off<br />

■ Related Parameters<br />

Bank * alarm value 1 to 3 (bank setting level): Page 211, 212, 213<br />

Bank * alarm value upper limit 1 to 3 (bank setting level): Page 212, 213, 214<br />

Bank * alarm value lower limit 1 to 3 (bank setting level): Page 212, 213, 214<br />

Alarm 1 to 3 type (initial setting level): Page 231 to 234<br />

Standby sequence reset: Page 244, Auxiliary output * open in alarm: Page<br />

245, HB ON/OFF: Page 246, Alarm 1 to 3 hysteresis: Page 233 (advanced<br />

function setting level)<br />

Event input assignment 1 to 4 (initial setting level): Page 238<br />

HB ON/OFF: Page 246, PF setting: Page 273 (advanced function setting<br />

level)<br />

prlt Move to Protect Level Time<br />

Function<br />

Setting<br />

See<br />

sero Input Error Output<br />

Function<br />

Setting<br />

This parameter sets the key pressing time required to move to the protect<br />

level from the operation level, the adjustment level, bank setting level, PID<br />

setting level, or monitor/setting item level.<br />

Setting range Unit Default<br />

1 to 30 Second 3<br />

■ Related Parameters<br />

Operation/adjustment protect, Initial setting/communications protect, Setting<br />

change protect (protect level): Page 172<br />

Alarm 1 must be assigned, but not to<br />

a work bit output.<br />

When this parameter is set to ON, the output assigned for alarm 1 turns<br />

ON for input errors.<br />

Note For details on input errors, refer to Error Displays on page 304.<br />

The alarm 1 output is an OR output between alarm 1, HB alarm/HS<br />

alarm, heater overcurrent alarm, and input error.<br />

Output is turned OFF when switching to the initial setting level, communications<br />

setting level, advanced function setting level, or calibration level.<br />

251