Wiring Terminals Section 2-2<br />

Communications RS-485<br />

38<br />

When communications are to be used with the E53-CN@03N2 for the<br />

E5CN-H, or E53-EN03 for the <strong>E5AN</strong>/EN-H, connect communications<br />

cable across terminals 11 and 12 or 21 and 22.<br />

11<br />

12<br />

E53-CN@03N2 (for E5CN-H)<br />

Specify both ends of the transmission path including the host computer as<br />

end nodes (that is, connect terminators to both ends).<br />

The minimum terminal resistance is 54 Ω.<br />

Communications Unit Connection Diagram<br />

E5CN-H<br />

<strong>E5AN</strong>/EN-H<br />

− +<br />

FG<br />

A < B: [1] Mark<br />

A > B: [0] Space<br />

B(+)<br />

A(−)<br />

RS-485<br />

Host computer<br />

RS-485 Shield<br />

Host computer<br />

RS-485<br />

−<br />

+<br />

FG<br />

A < B: [1] Mark<br />

A > B: [0] Space<br />

11<br />

12<br />

13<br />

21<br />

22<br />

B(+)<br />

A(−)<br />

Do not use.<br />

B(+)<br />

RS-485<br />

E53-EN03 (for <strong>E5AN</strong>/EN-H)<br />

The RS-485 connection can be either one-to-one or one-to-N. A maximum<br />

of 32 Units (including the host computer) can be connected in oneto-N<br />

systems. The maximum total cable length is 500 m. Use AWG24<br />

(cross-sectional area: 0.205 mm2 ) to AWG14 (cross-sectional area:<br />

2.081 mm2 ) shielded twisted-pair cable.<br />

A(−)<br />

E5CN-H (No. 1) E5CN-H (No. 31)<br />

RS-485<br />

RS-485<br />

No. Abbreviation No. Abbreviation<br />

12 A (−)<br />

12 A (−)<br />

11 B (+)<br />

11 B (+)<br />

Shield<br />

Terminator (120 Ω, 1/2 W)<br />

<strong>E5AN</strong>/EN-H (No. 1)<br />

<strong>E5AN</strong>/EN-H (No. 31)<br />

RS-485 RS-485<br />

No. Abbreviation<br />

No. Abbreviation<br />

22 A (−)<br />

22 A (−)<br />

21 B (+)<br />

21 B (+)<br />

12 A (−)<br />

12 A (−)<br />

11 B (+)<br />

11 B (+)<br />

Terminator (120 Ω, 1/2 W)<br />

Cross-sectional area of<br />

conductor<br />

AWG24: 0.205 mm 2<br />

AWG14: 2.081 mm 2