Adjustment Level Section 5-4<br />

sprt SP Ramp Set Value<br />

Function<br />

Setting<br />

See<br />

The ST parameter must be set to<br />

OFF.<br />

This parameter sets the rate of change during SP ramp operation. Set the<br />

maximum permissible change width per unit of time as the SP ramp set<br />

value. The SP ramp function is disabled if this parameter is set to OFF.<br />

During temperature input, the decimal point position of the SP ramp set<br />

value is dependent on the currently selected sensor, and during analog<br />

input it is dependent on scaling.<br />

The set value is saved in the SP Ramp Set Value parameter for the current<br />

bank.<br />

Setting range Unit Default<br />

OFF or 1 to 32400 EU/s or EU/minute off<br />

■ Related Parameters<br />

Input type: Page 224, Scaling upper limit, Scaling lower limit, Decimal point<br />

(initial setting level): Page 226, ST: Page 228 (initial setting level)<br />

SP ramp time unit (advanced function setting level): Page 244<br />

Bank * SP ramp set value (bank setting level): Page 211<br />

ol-h MV Upper Limit The control must be set to 2-PID<br />

control.<br />

The ST parameter must be set to<br />

ol-l MV Lower Limit<br />

Function<br />

Setting<br />

OFF.<br />

Position-proportional (close) control<br />

must be supported.<br />

The MV Upper Limit and MV Lower Limit parameters set the upper and<br />

lower limits of the manipulated variable. When the calculated manipulated<br />

variable exceeds the upper or lower limit value, the upper or lower limit<br />

value will be the output level.<br />

The set value is saved in the MV Upper Limit and MV Lower Limit parameters<br />

for the current PID set.<br />

MV Upper Limit<br />

The setting ranges during standard control, heating/cooling control, and<br />

position-proportional (close) control are different.<br />

Control method Setting range Unit Default<br />

Standard MV lower limit + 0.1 to 105.0 % 105.0<br />

Heating/cooling 0.0 to 105.0<br />

Position proportional<br />

(close)<br />

MV lower limit + 0.1 to 105.0<br />

205