Counting Control Output ON/OFF Operations Section 4-21<br />

Initial Setting Level 2. Select the Move to Advanced Function Setting Level parameter by press-<br />

Move to Advanced<br />

Function<br />

Setting Level<br />

ing the M Key.<br />

Advanced Function Setting Level 3. Press the D Key to enter the password (−169). It is possible to move to<br />

4-21 Counting Control Output ON/OFF Operations<br />

4-21-1 Control Output ON/OFF Count Function<br />

150<br />

amov<br />

-169<br />

init<br />

off<br />

pf<br />

a-m<br />

pf<br />

pfdp<br />

pfd1 1<br />

pfd1 7<br />

Parameter<br />

Initialization<br />

PF Setting<br />

PF Setting<br />

Monitor/Setting<br />

Item 1<br />

Monitor/Setting<br />

Item 1<br />

the advanced function setting level by either pressing the M Key or waiting<br />

two seconds without pressing any key.<br />

4. Press the M Key to select the PF Setting parameter.<br />

5. Press the U Key to select PFDP (Monitor/Setting Item).<br />

6. Press the M Key to select the Monitor/Setting Item 1 parameter.<br />

7. Press the U Key to select 7 (Alarm Value 1).<br />

Initial Setting Level 8. Press the O Key for at least one second to move from the advanced<br />

Input Type<br />

function setting level to the initial setting level.<br />

in-t 5<br />

Operation Level 9. Press the O Key for at least one second to move from the initial setting<br />

C<br />

alm<br />

level to the operation level.<br />

25.0<br />

100.0<br />

Monitor/Setting Item Level 10. Press the PF Key to display Alarm Value 1 for the current bank.<br />

C<br />

al-1<br />

0.0<br />

▲<br />

▲<br />

Monitor/Setting<br />

Item Display 1<br />

If Control Output 1 and 2 are ON/OFF outputs (relay outputs, voltage outputs<br />

for driving SSR, or SSR outputs), the number of times that a control output<br />

turns ON and OFF can be counted. Based on the control output ON/OFF<br />

count alarm set value, an alarm can be output and an error can be displayed if<br />

the set count value is exceeded.<br />

The default setting of the Control Output ON/OFF Alarm Set Value parameter<br />

is 0. ON/OFF operations are not counted when this parameter is set to 0. To<br />

enable counting ON/OFF operations, change the setting to a value other than<br />

0.