Using the Simple Program Function Section 4-16<br />

4-16 Using the Simple Program Function<br />

4-16-1 Simple Program Function<br />

Parameters Related to the Simple Program Function<br />

132<br />

A simple program consists of multiple banks.<br />

The program can be created from the required number of banks by specifying<br />

the end bank in the Valid Program Bank parameter.<br />

A simple program can be started from any of the banks from bank 0 to the<br />

end bank. When operation is finished in one bank, the program switches<br />

to the next bank and operation starts in that bank. Operation after the end<br />

bank has been completed can be set in the Program Pattern parameter.<br />

The program starts when the Program Start parameter is changed from<br />

RSET to STRT.<br />

The program stops when the Program Start parameter is changed from<br />

STRT to RSET. The program can be reset in any bank.<br />

SP0<br />

Soak time 0<br />

(Bank 0)<br />

SP1<br />

Wait band 0<br />

Wait band n<br />

Wait band 1<br />

Soak time 1 Soak time n<br />

Parameter name Symbol Set (monitor) values Unit Display level<br />

Program Pattern ptrn OFF, STOP, CONT, LOOP --- Initial setting level<br />

Program Start prst RSET, STRT --- Operation level<br />

Bank ∗ Soak Time<br />

(See note 2.)<br />

∗ sok 0 to 9999 min or h Bank setting level<br />

Soak Time Unit t-u m (minutes)/h (hours) --- Advanced function setting<br />

level<br />

Bank ∗ Wait Band ∗ wtb Temperature: OFF, 0.1 to 3,240.0 °C or °F (See note 1.) Bank setting level<br />

(See note 2.)<br />

Analog: OFF, 0.01 to 99.99<br />

Soak Time Remain<br />

Monitor<br />

sktr 0 to 9999 min or h Operation level<br />

Valid Program Bank<br />

(See note 3.)<br />

pbnk 0 to 7 --- Initial setting level<br />

(Bank 1)<br />

(Bank n)<br />

Note (1) The setting unit is %FS for analog inputs.<br />

(2) When the Soak Time or Wait Band parameter is changed in the adjustment<br />

level, the changes will be reflected in the current bank.<br />

(3) Displayed when the Program Pattern parameter is set to any value other<br />

than OFF. The bank cannot be switched to any other bank.<br />