Advanced Function Setting Level Section 5-10<br />

sub1 Auxiliary Output 1 Assignment Auxiliary output 1 must be assigned.<br />

Function<br />

Setting<br />

See<br />

This parameter sets the function to be assigned to auxiliary output 1.<br />

Note (1) If c-o is assigned for standard control, a value equivalent to 0% will be<br />

output.<br />

(2) Can be selected when the Program Pattern parameter is set to OFF, but<br />

the function will be disabled.<br />

(3) If a setting is changed when the Program Pattern parameter is not set to<br />

OFF, control automatically switches to p.end.<br />

(4) WR1 to WR8 are not displayed when the logic operation function is not<br />

used.<br />

■ Related Parameters<br />

Program pattern (initial setting level): Page 229<br />

Setting range Default<br />

none: No function is assigned to auxiliary output 1. alm1<br />

o:<br />

c-o:<br />

Heating control output is output.<br />

Cooling control output is output. (See note 1.)<br />

(See note<br />

3.)<br />

alm1: Alarm 1 is output.<br />

alm2: Alarm 2 is output.<br />

alm3: Alarm 3 is output.<br />

p.end: Program end is output. (See note 2.)<br />

ralm: Control output ON/OFF count alarm<br />

wr1: Work bit 1 (See note 4.)<br />

wr2: Work bit 2 (See note 4.)<br />

wr3: Work bit 3 (See note 4.)<br />

wr4: Work bit 4 (See note 4.)<br />

wr5: Work bit 5 (See note 4.)<br />

wr6: Work bit 6 (See note 4.)<br />

wr7: Work bit 7 (See note 4.)<br />

wr8: Work bit 8 (See note 4.)<br />

263